0x2005 Homing Options

Name Index:Sub Type Bit Size Min Data Max Data Default Data Unit Access PDO Mapping
Home Position 0x2005:1 DINT 32 0 Inc readonly (default)

Home Position (Encoder position at home), from which axis is referenced. The units are user-defined (increments of the position encoder by default; see 0x6092 Feed constant to change it).

Name Index:Sub Type Bit Size Options Unit Access PDO Mapping
Restore Home Position when loading configuration 0x2005:2 USINT 8
NO 0
YES 1
readwrite

 

Value Definition
0 No - Home Position will not be persistent after powercycle, user would need to home again.
1 Yes - Home Position will be persistent after powercycle, axis will be referenced with the home position saved in config.

 

Name Index:Sub Type Bit Size Min Data Max Data Default Data Unit Access PDO Mapping
Torque Threshold for Homing on end stop 0x2005:3 UINT 16 0 0 readwrite

Absolute value of the torque threshold (in ‰ of rated torque) at which the controller will consider that the end stop has been met. Used for methods -1 to -4.

Name Index:Sub Type Bit Size Min Data Max Data Default Data Unit Access PDO Mapping
Offset From Endstop 0x2005:4 UINT 16 0 Inc readwrite

Absolute position value from Endstop where the axis needs to be homed. Used with methods -3 and -4. The units are user-defined (increments of the position encoder by default; see 0x6092 Feed constant to change it).